Vortex FP

Crowcon Vortex FP, gas detection control panel

Manufacturer
Crowcon
Reference
Vortex FP

Specifications

Product
Crowcon Vortex FP, gas detection control panel
Size
440 x 640 x 332mm (17.3 x 25 x 13 ins) 450 x 330 x 289mm (17.6 x 13 x 11.4 ins)
Weight
70Kgs (154lbs) approx. 37.5kgs (83lbs) approx.
Enclosure material
LM25 aluminium with polyester powder coating
Ingress protection
IP66 Channels Up to 12 (1 to 3 4-way input modules)
Operating temperature
-10°C to +40°C (14°F to +140°F)
Humidity
0-95% RH non-condensing Inputs
Gas
2 or 3 wire 4-20mA (sink or source), 0-5V Fire – smoke & heat detectors, manual call-points Up to 3 loops, Up to 20 devices per loop
Outputs
External audible/visual alarm drive Via relays, four 24Vdc 0.5A supplies provided. Relays Type Up to 32 SPCO with bus extension module Relay limitations: 1 or 2 input modules: 2 relay modules max. (16 relays) 3 input mod
Event logging
Up to 300 alarm, power, fault, system events are stored in Non-Volatile Memory Panel indication Channel number:  2-digit 7-segment Green LED Gas reading: 4-digit 7-segment Red LED Measurement units:  % LEL, ppm, % Vol, F
Power
AC mains/DC: 110 or 240Vac 3.2A max 150W PSU 20 – 30Vdc 85 – 264Vac 0.8A max 75W PSU 20 – 30Vdc Battery back-up: not available
Approvals
Low voltage directive: EN61010-1 EMC: Directive 2014/30/EU: EN50270, FCC: CRF47 Part 15, ICES-003 ATEX: Ex II 2G D Zone 1, Zone 2, IECEx optional Functional safety Validated to IEC61508 downloads Certificate Vortex FP En
Description
Ideal for use in Zone 1 or Zone 2 hazardous areas, the Vortex FP and FP Compact are fireproof and highly durable, with a display fitted with magnetic switches which enables the system to be interrogated or inhibited without opening the system enclosure. Available in two sizes, there is a Vortex FP s

Add this reference to my quote

Set the quantity and delivery on the interactive catalogue.

Request a quoteAll references for this item

Other references in this line