Xgard Bright

Crowcon Xgard Bright, fixed gas detector

Manufacturer
Crowcon
Reference
Xgard Bright

Specifications

Product
Crowcon Xgard Bright, fixed gas detector
Size
Aluminium enclosure: ATEX/IECEx: 156 x 166 x 109 mm (6.1 x 6.5 x 4.3 inch) UL: 162 x 166 x 110 mm (6.4 x 6.5 x 4.3 inch) Stainless Steel Enclosure: ATEX/IECEx: 165 x 166 x 105 mm (6.1 x 6.5 x 4.1 inch) UL: 162 x 166 x 10
Power
3W max Electrical Output 3-wire 4-20mA (Sink or Source) RS-485 Modbus RTU HART 7 (Optional)
Weight
Aluminium enclosure: ATEX/IECEx: 1kg (2.2 lbs) UL: 1.5 kg (3.31 lbs) Stainless Steel Enclosure: ATEX/IECEx: 3.1 kg (6.8 lbs) UL: 3.5 kg (7.72 lbs) Enclosure Material ADC 12 aluminium alloy or 316 stainless steel Relay Al
Humidity
0 to 95% RH, non-condensing Contact Crowcon for sensor operating humidity range. Repeatability +/- 2% FSD Zero drift +/- 2% FSD per year maximum
Ingress protection
IP65/66, EN 60529 Hazloc Standards & Approvals ATEX: EN IEC 60079-0, EN 60079-1, EN 60079-31 IECEx: IEC 60079-0, IEC 60079-1, IEC 60079-31 Zone 1 and Zone 2 or Zone 21 and Zone 22 Aluminium: Ex II 2 G Ex db IIC T6 Gb Tam
Approvals
UL, IECEx, ATEX, CE, INMETRO, ECAS, PESO, CNEx, UC, CCSA TA, MED EMC Compliance EN 50270, EN IEC 61326-1, EN 55011, CISPR 11, EN 61000-4 Zones Certified for use in Zone 1 and Zone 2 areas
Warranty
2 years on transmitter 5 years on MPS flammable and O2 Long Life sensor 2 years on IR flammable sensors Refer to GEN067 – Warranty Periods for other sensors Gases and Ranges – xgard bright
Gas
Sensor type Gas range Temp range °C Flammable gases (Tested for Methane, Butane, Ethane, Ethylene, Hydrogen, LPG, Pentane, Propane) MPS 0-100% LEL -40 to +75 Butane (C 4 H 10) Infrared 0-100% LEL -40 to +60 Hydrogen (H
Gas
Sensor type Gas range Temp range °C Flammable gases* MPS 0-100% LEL -40 to +75 Ammonia (NH3) Electrochemical 0-50, 100 ppm -40 to +50 Chlorine (CL 2) Electrochemical 0-5, 10 ppm -20 to +50 Hydrogen Cyanide (HCN) Electro
Description
Xgard Bright is a versatile detector offering flammable and toxic gas detection and oxygen monitoring, while providing ease of operation and reduced installation costs.